at High Density Housing / Commercial - Addition / Alteration - Elevator modernization Interior alterations to provide elevator modernization to the existing addressable two-stage fire alarm system to incorporate emergency recall of 11 elevators to meet the requirements of CSA-B44 in Bentall 3 commercial building. Scope of work: - Addition of new addressable smoke detectors in elevator lobbies - Replacement of elevator controller and cab light fusible disconnect switches - Replacement of existing elevator machine room and elevator pit receptacles with GFCI type receptacles. - Replacement of elevator machine room and elevator pit luminaires with new LED luminaires c/w wireguard. - Provision of new exit signs (green pictogram) along the egress path on the Main and Alternate Recall Levels. - Provision of “elevator of emergency power” and “pre/post-transfer” signals from the existing ATS to the new elevator controllers. ******THIS PERMIT HAS BEEN REVIEWED AND ISSUED UNDER THE REQUIREMENTS OF VBBL 2019 ******** Building Review Branch Notes: 1. Sch A, Arch. Sch B, Elec. Sch B submitted 2. Automatic emergency recall (Elevator 1-5: Main - ground floor, Alternate - Level 17)(Elevator 6-10: Main - ground floor, Alternate - Level 4) (Service Elevator: Main - B level, Alternate - LM level) · 595 BURRARD STREET, Vancouver, BC V7X 1K8 · Vancouver, BC